Tyco CIM800 Contact Input Module with M520 Cover Minerva MX (555.800.032) The CIM800 Addressable Contact Input Module supervises two circuits of voltage-free contacts such as outputs from extinguishing systems, ventilation controls, fire door controls, sprinkler flow switches, non-indicating detectors, etc. The LED illuminates when any input goes into alarm, and can also be programmed to blink when polled by the Tyco MX Control and Indicating Equipment (CIE.). The CIM800 can be configured to supervise: Two circuits of multiple normally-open contacts; with short circuit alarm. Two circuits of multiple normally-closed contacts; open circuit alarm. Two circuits with a single normally-open contact closing for alarm; with short circuit fault. This requires a resistor in series with the alarm contact and special programming at the MX4428 CIE. On the MX4428, the two circuits are presented as a single addressable point; either circuit in alarm puts the point into alarm, any circuit in fault puts the point into fault. Key Features MX Addressable Module Supervise Two Circuits Supervise Multiple Contacts per Circuits Up to 250 Devices per Loop

Tyco CIM800 Contact Input Module with M520 Cover Minerva MX
(555.800.032)

The CIM800 Addressable Contact Input Module supervises two
circuits of voltage-free contacts such as outputs from
extinguishing systems, ventilation controls, fire door
controls, sprinkler flow switches, non-indicating detectors,
etc. The LED illuminates when any input goes into alarm, and
can also be programmed to blink when polled by the Tyco MX
Control and Indicating Equipment (CIE.).

The CIM800 can be configured to supervise:

Two circuits of multiple normally-open contacts; with short
circuit alarm.
Two circuits of multiple normally-closed contacts; open
circuit alarm.
Two circuits with a single normally-open contact closing for
alarm; with short circuit fault. This requires a resistor in
series with the alarm contact and special programming at the
MX4428 CIE.
On the MX4428, the two circuits are presented as a single
addressable point; either circuit in alarm puts the point
into alarm, any circuit in fault puts the point into fault.

Key Features

MX Addressable Module
Supervise Two Circuits
Supervise Multiple Contacts per Circuits
Up to 250 Devices per Loop